NFPA Standard-Specific Requirements
Ademco Contact ID Typical Printout
132
GF505 & GF510 Series PN 53164:A 3/26/2007
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the GF505/GF510 may be used to trip any dialer UL listed for
Central Station/Remote Station Reporting Services.
Figure B.1 GF505/GF510 FACP Connection to 411UD
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Relay Output (DACT Trouble) from 411UD
FACP Supervisory Relay
FACP Alarm Relay
FACP Trouble Relay
J4 Not Installed
411UD
1
2
3
4
5
6
7
8
+ 24 VDC nonresettable power
- 24 VDC nonresettable power
2.2K ELRs P/N 27070
1
2
3
4
5
6
7
8
9
1 2 3 4 5 6 7 8 9
FACP
Jumper -VDC to Trouble Relay contact
Trouble Input
(non-supervised,
power-limited)