CHAPTER 4 PARAMETER
Extended Function Setting Parameters
4-89
4
If upgrading from the ALPHA5 Series, by setting "0000" to "0005", the values will be the
same as those for ALPHA5 parameter settings PA2_61 to 63.
In this case, the deceleration operation when performing a forced stop or following OT
detection will be fixed at rapid deceleration.
Furthermore, the action sequence following either a minor or major failure alarm will be
based on the PA2_62 setting.
(With the ALPHA5 Series, the dynamic brake is applied and the motor decelerates when a
major failure alarm occurs, regardless of the PA2_62.)
The STO operation is based on the operation setting when PA2_61 servo-on is OFF.
(When servo-on is OFF, however, the operation when decelerating will be "dynamic brake operation"
when "Rapid deceleration" is set.)
PA2_64 Torque keeping time to holding brake
No.
Name
Setting range
Default
value
Change
64
Torque keeping time to
holding brake
0.00 [s] to 9.99 [s]
0.00
Always
Assign the "brake timing (function No. 14)" signal to the output signal.
The reference value of this parameter indicates the delay taken from shutoff of servo-on (function No.
1) CONT input signal to free-run.
Specify a time larger than the one taken from excitation of the brake to actual brake application.
The brake timing signal is turned off when servo-on is turned off.
PA2_65 Regenerative resistor selection
No.
Name
Setting range
Default
value
Change
65
Regenerative resistor
selection
0: None
1: Internal resistor 2: External resistor
1
Power
Select the regenerative resistor.
If the reference value is 1, the temperature of the regenerative resistor is calculated inside the amplifier
and monitored as a regenerative thermal value. 100 [%] indicates an overheated internal regenerative
resistor (RH1).
To install an external regenerative resistor for elevator operation or high operation frequency, set at 2.
If the reference value is 2, connect the thermistor of the external resistor to the external regenerative
resistor overheat (function No. 34).
Because of a normally closed contact, shutoff indicates an overheated external regenerative resistor
(RH2).
Содержание ALPHA7
Страница 1: ......
Страница 3: ...ii...
Страница 22: ...0 1 CHAPTER 0 INTRODUCTION 0...
Страница 36: ...1 1 CHAPTER 1 INSTALLATION 1...
Страница 47: ...CHAPTER 1 INSTALLATION 1 12 Servo Amplifier 1...
Страница 48: ...2 1 CHAPTER 2 WIRING 2...
Страница 163: ...CHAPTER 2 WIRING 2 116 Safety Function 2...
Страница 164: ...3 1 CHAPTER 3 OPERATION 3...
Страница 192: ...4 1 CHAPTER 4 PARAMETER 4...
Страница 317: ...CHAPTER 4 PARAMETER 4 126 Extension Function 2 Setting Parameters 4...
Страница 318: ...5 1 CHAPTER 5 SERVO ADJUSTMENT 5...
Страница 353: ...CHAPTER 5 SERVO ADJUSTMENT 5 36 Special Adjustment Vibration Suppression 5...
Страница 354: ...6 1 CHAPTER 6 KEYPAD 6...
Страница 408: ...7 1 CHAPTER 7 MAINTENANCE AND INSPECTION 7...
Страница 434: ...8 1 CHAPTER 8 SPECIFICATIONS 8...
Страница 460: ...9 1 CHAPTER 9 CHARACTERISTICS 9...
Страница 472: ...10 1 CHAPTER 10 PERIPHERAL EQUIPMENT 10...
Страница 516: ...11 1 CHAPTER 11 ABSOLUTE POSITION SYSTEM 11...
Страница 523: ...CHAPTER 11 ABSOLUTE POSITION SYSTEM 11 8 Calculation of Battery Life 11...
Страница 524: ...12 1 CHAPTER 12 POSITIONING DATA 12...
Страница 540: ...13 1 CHAPTER 13 MODBUS RTU COMMUNICATION 13...
Страница 579: ...CHAPTER 13 MODBUS RTU COMMUNICATION 13 40 Communications Procedures 13...
Страница 580: ...14 1 CHAPTER 14 PC LOADER 14...
Страница 614: ...STANDARDS COMPLIANCE CHAPTER 15 15...
Страница 628: ...CHAPTER 16 APPENDIXES 16...
Страница 661: ...CHAPTER 16 APPENDIXES 34 Product Warranty 16 16 7 Product Warranty...
Страница 662: ......