SPECIFICATIONS
Common Specifications
141
SPECIFICATIONS
Common Specifications
Cooling Method
Forced air cooling by internal fans
Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 symmetrical amperes (rms) when
protected by suitable Class J fuses.
Agency Approvals
UL and cUL listed, CE, marked.
CO
NT
RO
L
Control Method
Pulse Width Modulation (PWM) with V/F and SVC (Sensorless Vector Control) for IM and PM motors.
Frequency Setting Resolution
Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz)
Analog Reference: [Max. output frequency] x 0.03/60Hz (±11 bit)
Frequency Accuracy
Digital: ± 0.01 % of Max. Output Frequency. Analog: ± 0.1 % of Max. Output Frequency.
V/F Control Curve
12 preset V/F curves and four-point square curve
Overload Capacity
Variable Torque: 120% of VFD rated current for 1 minute during every 5 minutes of operation.
Constant Torque: 150% of VFD rated current for 1 minute during every 5 minutes of operation and 160% for 3 seconds
during every 25 seconds of operation.
Starting Torque
Up to 150% or higher at 0.5Hz (Torque Accuracy ±5%).
Torque Limit (Stall level)
Variable Torque: Max. 130% torque current; Constant Torque: Max. 160% torque current
OP
ER
AT
IO
N
Operation Method
Keypad / Terminals / RS-485 BACnet or Modbus Communication / Optional Modbus TCP/IP & Ethernet IP.
Frequency Setting
Two Analog Inputs 0- 10VDC/ 4- 20mA and One AI 0-10VDC. Digital input: Keypad or Communication
In
pu
ts
Start Signal
Forward, Reverse and Jog (some features can start and stop VFD based on analog signal).
Digital Inputs
8 programmable digital inputs can be set to any selection from long list of functions.
Multi-Step
Up to 17 Speeds can be set including Jog by Programmable Digital Inputs.
Accel/Decel Time and Presets
0.00- 600.00/0.0- 6000.0 seconds. Three ACC/DEC preset values switched by digital inputs or one by frequency. Addi
-
tional adjustable Accel/Decel S-Curve pattern.
Emergency Stop
Ext. Trip and Shutdown immediately interrupt VFD output in any control method.
Jog
Jog Operation with adjustable Jog frequency
Fault Reset
Resets VFD via keypad, digital input, or communication. Some critical faults must be reset by recycling power.
Safety Inputs
SCM and STO terminals for safety circuit wiring.
Ou
tp
uts Three Multi-Function Relays
One relay with Form C: 250VAC 3A/30VDC, 3A (resistive) 1.2A (inductive) contact; Two relays with Form A: 250VAC
1.2A/30VDC 3A (resistive) 1.2A (inductive). Each relay can be programmed to any selection from the functions list.
Two Analog Outputs
Selections: Output Frequency, Output Current, Output Voltage, Output kW, DC Link Voltage, AVI1, ACI, AVI2 AI signal
level. Both outputs are 0-10VDC scalable from 10 to 200%.
General Operation Functions
DC Braking, Frequency Limit, Jump Frequencies, 2nd ACC/DEC, Auto Restart, Auto-Tuning, PID w/sleep, Flying Start,
Speed Search, DC Braking, Slip Compensation, Motor Pre-heat, Temperature Foldback, Damper Control, Fireman’s Over
-
ride, Shutdown, Power-on Delay, Run Delay, Minimum Run Timer, PM Motor and MagForce Control and Auto-Tuning
Pump Operation Functions
Sleep Mode with Pressure Boost, Pipe Fill, PID, Overpressure, ULD (Underload), HLD (High Load), Broken Pipe, Backspin
Timer, MMC, Lubrication, Screen Clean, No-Flow Protection, Pump Prime Time
PR
OT
EC
TIO
N
VFD Fault Trips
Over Voltage, Low Voltage, Over Current, Overload, Short Circuit, Ground Fault, VFD Overheat, Input Phase Loss, Output
Phase Open, CPU Communication Error, Signal Loss, Hardware Fault, etc.
VFD Alarm
Stall Prevention at ACC and DEC, Overload, Thermal Sensor Fault, Capacitors High Temperature, Signal Loss, Overpres
-
sure, Underload, High Load, etc.
Overcurrent
200/208/230/460VAC Variable Torque: At 200% of VFD rated current
200/208/230/460VAC Constant Torque: At 240% of VFD rated current
Current clamp: Variable Torque: 130- 135%, Constant Torque 170- 175%
575VAC models: At 225% VFD rated current
Current clamp: Variable Torque: 128- 141%, Constant Torque: 170- 175%
Overvoltage
230VAC models: At 410VDC DC bus voltage
460VAC models: At 820VDC DC bus voltage
575VAC models: At 1016VDC DC bus voltage
Fault History
Keypad provides 6 fault records. VFD logs 30 faults.
EN
VIR
ON
M
EN
T
Operating Temperature
NEMA 1: 14°F ~ 104°F (-10°C ~ 40°C), Open Type: 14°F ~ 122°F (-10°C ~ 50°C)
Storage Temperature
-13°F ~ 158°F (-25°C ~ 70°C)
Ambient Humidity
Up to 95% RH. (Non-Condensing)
Altitude
Normal up to 3,300ft (1,000m). At altitude up to 2,000 m, de-rate by 1% of rated current or lower 0.5 ºC of temperature
for every 100m above 1,000m. Maximum altitude for Corner Grounded TN system is 2,000m. For application over
2,000m, please contact Technical Support.
Vibration and Impact
1mm peak to peak value from 2Hz to 13.2Hz; 0.7G- 1.0G from 13.2Hz to 55Hz; 1.0G from 55Hz to 512Hz. Comply with IEC
60068-2-6 and IEC/EN60068-2-27.
Environmental Conditions
Pollution degree 2. No Corrosive Gas, Combustible Gas, Oil Mist or Dust. IEC60721-3-3/ IEC60364-1/ IEC60664-1.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...