PARAMETER REFERENCE TABLES
Parameter Descriptions > ADV Menu
128
Parameter Descriptions > ADV Menu
AR = Adjustable while running.
CODE Mod
Bus AR Display Name
Range
Description
ADV-00 0768 Y Upper Bound Int 0 to 100%
Upper limit for the integral gain (I), which limits the output frequency.
Upper Limit Freq = VFD Max Freq Main [VFD-00] x Upper Bound Int [ADV-
00].
Too large integral value will cause a slow response to sudden load changes.
This could cause motor stall or machine damage.
ADV-01 0769 Y PID Out Limit
0 to 110%
Maximum PID command limit. Percentage of Maximum Output Frequency
[VFD-00].
ADV-02 0770 Y Password Input
0 to 65535
Password protect from modifying parameters.
ADV-03 0771 N Parameter Reset 0_Disabled
1_Write protect
2_
3_Reset KWH
4_Reset all Param
5_Reset M Run T
Select stored data to be reset.
ADV-05 0773 Y Password Lock
0_Unlocked
1_Locked
When setting password protection for the first time, set password in Pass
-
word Input [ADV-02] and then Password Lock [ADV-05] becomes 1-
Locked. To permanently disable password protection, unlock parameters by
entering password in Password Input [ADV-02] and then set Password
Lock [ADV-05] to 0-Unlocked. If drive is unlocked by a password and pass
-
word lock is not set to 0-Unlocked, the next reboot of the VFD will lock the
VFD again.
ADV-06 0774 Y Acc/Dec Type
0_Linear Acc/Dec
1_Auto Acc/L-Dec
2_L-Acc/Auto Dec
3_Auto Acc/Dec
4_Lin, Auto Stall
Provides automated acceleration and deceleration with stall prevention.
0_Linear Acc/Dec: Accelerates and decelerates according to the setting of
SET-11~12 and VFD-19~24.
1_Auto Acc/L-Dec: Auto detects the load torque and accelerates for the
fastest acceleration time and smoothest start current. Deceleration is linear
according to setting of SET-11-12 and VFD-19-24.
2_L-Acc/Auto Dec: Linear acceleration according to setting SET-11~12 and
VFD-19~24. Auto detects the load re-generation and stops the motor
smoothly with the fastest decel time.
3_Auto Acc /Dec: Auto detects load for smoothest operation for accelera
-
tion and deceleration.
4_Lin, Auto Stall: Stall prevention by auto accel./decel being limited by
SET-11~12 and VFD-19~24.
ADV-07 0775 N Acc/Dec Format 0_Unit 0.01 Sec
1_Unit 0.1 Sec
Precision of acceleration and deceleration.
ADV-08 0776 Y Energy Saving
0_Disable
1_Enable
When the output frequency is constant, the output voltage will auto
decrease by the load reduction. The drive will operate with minimum
power.
ADV-09 0777 Y E-Saving Gain
10 to 1000%
Determines speed of adjusting output voltage in relationship to load reduc
-
tion. If the motor oscillates or has a quick temperature rise, the value should
be increased.
ADV-10 0778 N MMC Mode
0_Disabled (default)
1_Equal Run Time
2_Soft Start mode
3_Lead-Lag
4_Run Time Alt
5_Rotate Lead
Type of operation for Multi-Motor Control.
ADV-11 0779 N Motor Quantity
1 (default) to 7
Number of motors in MMC relay control setup. Limit is 3 without I/O card.
When I/O card is installed, selections 1-7 are available.
ADV-12 0780 N Aux Mtr Stop Hz 0 to VFD-00
When output frequency is less than value and remains for duration of ADV-
15, motors will be shut down one by one.
ADV-13 0781 N Alt Run Time
0.0 to 60000 Min
Duration of running a motor before switching to another motor.
ADV-14 0782 N S-Start ON Dly
0.0 to 3600 Sec
Delay time before switching on motor.
ADV-15 0783 N S-Start Off Dly
0.0 to 3600 Sec
Delay time before switching off motor.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...