MAINTENANCE
Troubleshooting
104
Damper Fault (DPR)
• Damper limit switch has not
closed in time to start fan motor;
or, switch has opened for more
than 2 seconds while motor is
running.
• Check limit switch connections and function
• Check damper relay connections and damper function
• Verify all damper related parameters
Dec Energy Back (dEb)
• Deceleration energy backup
error. When ADV2-28 is not
disabled and power is off or
momentarily off, VFD will display
dEb during accel./decel. stop.
• Check if input power is stable
Derating Error (oL3)
• The VFD detects excessive drive
output current.
• Check if the motor is overloaded.
EEPROM read err (cF2)
• Internal memory cannot be read. • Press “RESET” key
• Reset all parameters to default
• If error still exists, please call Technical Support..
EEPROM write err (cF1)
• Internal memory cannot be
programmed.
• Press “RESET” key
• Reset all parameters to default
• If error still exists, please call Technical Support.
Emergency stop (EF1)
• Emergency stop
• When a multi-function input terminal (MI1 to MI6) is set to
emergency stop and the contact is closed, the AC motor drive stops
output U, V, W and the motor coasts to stop.
• Press RESET after condition has been corrected.
External Fault (EF)
• External Fault
• Input EF (N.O.) on external terminal is closed to GND. Output U, V, W
will be turned off.
• Give RESET command after fault has been cleared.
Ground fault (GFF)
• Output current exceeds [PROT-
34] for more than [PROT-35]
time delay.
NOTE:
This protection is provided
for VFD, not to protect user.
• Check the wiring connections between the VFD and motor for
possible short circuits, also to ground.
• Check for possible poor insulation at the output.
• Verify grounding of communication circuit
• Ensure separation of communication circuits and high-voltage wiring
• Check whether the IGBT power module is damaged.
Guarding T-out (CGdE)
• CANopen guarding error. When
CANopen Node Guarding detects
that one of the slaves does not
respond.
• Increase guarding time and detection times.
• Verify wiring and grounding of communication circuit.
• Make sure communication circuit is wired in series.
• Use CANopen cable or add terminating resistance.
Heartbeat T-out (CHbE)
• CANopen heartbeat error. When
CANopen Heartbeat detects that
one of the slaves does not
respond.
• Increase heartbeat time
• Verify wiring and grounding of communication circuit.
• Make sure communication circuit is wired in series.
• Use CANopen cable or add terminating resistance.
Heat Sink oH (oH2)
• Capacitance temperature causes
heatsink overheating.
• Ensure that the ambient temperature falls within the specified
temperature range.
• Make sure heat sink is not obstructed. Check if the fan is operating
• Check if there is enough ventilation clearance for the drive.
High Load (HLD)
• Current or Torque is above [SET-
48] HLD Level and [SET-49] HLD
Frequency.
“High Load Detection” on page 75
Ias sensor Err (cd1)
• U-phase output error
• Cycle the power. If error still exists, please call Technical support.
Ibs sensor Err (cd2)
• V-phase output error
• Cycle the power. If error still exists, please call Technical support.
Ics sensor Err (cd3)
• W-phase output error
• Cycle the power. If error still exists, please call Technical support.
Fault
Description
Corrective Action
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...