COMMUNICATIONS
Modbus Communication
88
System Parameters Setup
•
HOA Mode Source [SET–60]:
Set to
2_RS485 Serial
. This enables Modbus to switch between Hand and
Auto modes.
•
Auto Speed Ref [SET–07]:
Set to
5_RS485 Serial
. This enables Modbus to control the speed when in Auto
mode.
•
Auto Run Cmd [SET–08]:
Set to
2_RS485 Serial
. This enables Modbus to initiate a Run Command in Auto
mode.
•
Hand Speed Ref [SET–09]:
Set to
1_RS485 Serial
. This enables Modbus to control the speed when in
Hand mode.
•
Hand Run Cmd [SET–10]:
Set to
2_RS485 Serial
. This enables Modbus to initiate a Run Command in Hand
mode.