ELECTRICAL INSTALLATION
Control Circuit Connections
45
Temperature Protection or PID Control with PT-100 or PTC Sensor:
•
Connect the sensor Positive wire to the AFM2 terminal. Place the AFM2
micro switch in the
DOWN
position.
•
Connect the sensor Negative wire to the ACM terminal.
•
Use a jumper wire to connect the AFM2 and AVI1 terminals. The AVI1 micro
switch should be in the
UP
position.
•
Any shield wire should be connected to Earth ground.
For specific parameter setups, please call Technical Support.
Speed Control using 0-10 VDC Potentiometer:
•
Connect the potentiometer Positive wire to the VFD +10V terminal.
•
Connect the potentiometer Output wire to the AVI1, AVI2, or ACI terminal.
The AVI1 micro switch should be in the
UP
position. If using the ACI termi
-
nal, the ACI micro switch should be
DOWN
.
•
Connect the potentiometer Com wire to the ACM terminal (signal ground).
•
Any shield wire should be connected to Earth ground.
•
AVI1 Input Select [IO–05]
or
ACI Input Select [IO–00]
should be set to
0-10V
.
•
Auto Speed Reference [SET–07]
or
Hand Speed Reference [SET–09]
should be set to
the chosen input.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...