PARAMETER REFERENCE TABLES
Parameter Descriptions > Option Menu
136
Parameter Descriptions > Option Menu
AR = Adjustable while running.
CODE
Mod
Bus AR Display Name
Range
Description
Option-00 1792 N M10 Define
0_No Function
1_Speed-L
2_Speed-M
3_Speed-H
4_Speed-X
5_Fault Reset
6_Jog Speed
7_Hold Speed
8_XCEL-L
9_XCEL-M
10_Ext. Trip
12_AVI1 Analog Spd
13_ACI Analog Spd
14_AVI2 Analog Spe
16_Digital Up
17_Digital Down
18_PID Disable
19_CLR CNT
20_Input CNT (MI6)
21_FWD Jog
22_REV Jog
25_E-Stop
26_HOA HAND
27_HOA AUTO
28_Drive Enabled
29_PLC mode bit 0
30_PLC mode bit 1
32_FO with RUN Cmd
33_FO w/o RUN Cmd
34_Damper Limit Sw
35_Shutdown N-Latch
36_Shutdown Latched
37_Flow Switch
40_Aux Motor-1 OFF
41_Aux Motor-2 OFF
42_Aux Motor-3 OFF
43_Aux Motor-4 OFF
44_Aux Motor-5 OFF
45_Aux Motor-6 OFF
46_Aux Motor-7 OFF
47_All Aux Mtr Off
Defines functionality of input MI10 on I/O extension card.
1_Multi-step speed command 1
2_Multi-step speed command 2
3_Multi-step speed command 3
4_Multi-step speed command 4
5_Use to reset fault after cause is corrected
6_Changes speed in jog mode to value set in VFD-55
7_When active, VFD will hold current speed
8_ACC/DEC time will be changed to VFD-19 and VFD-20
9_ACC/DEC time will be changed to VFD-21 and VFD-22
10_Trips VFD by external protective device and requires reset
12_In non-PID mode, changes speed reference to AVI1
13_In non-PID mode, changes speed reference to ACI
14_In non-PID mode, changes speed reference to AVI2
16_Increases speed reference when SET-07 is set to (1)
17_Decreases speed reference when SET-07 is set to (1)
18_Disables PID and switches speed reference to keypad
19_Clears pulse counter accumulated value (MI6 only)
20_Pulse counter input (MI6 only)
21_Jog Command Forward
22_Jog Command Reverse
25_VFD stops by Emergency Stop device (requires reset)
26_External HOA Hand position contact
27_External HOA Auto position contact
28_Enables and disables the drive (not a run command)
29_ PLC Function Disable 29 and 30=(0) or Run 29= (1)
30_ PLC Function Disable 29 and 30=(0) or Stop 30= (1)
32_VFD will start in FO Mode by FO DI and Run Command
33_VFD will start in FO Mode by FO DI (No Run Command)
34_When damper is closed, Damper LSW DI is activated
35_Activates Shutdown. When inactive, VFD operates normally
36_Activates Shutdown. Requires reset to operate normally
37_Detects water or air flow by Flow Switch
40_Aux Motor-1 in MMC mode is off sequence
41_Aux Motor-2 in MMC mode is off sequence
42_Aux Motor-3 in MMC mode is off sequence
43_Aux Motor-4 in MMC mode is off sequence
44_Aux Motor-5 in MMC mode is off sequence
45_Aux Motor-6 in MMC mode is off sequence
46_Aux Motor-7 in MMC mode is off sequence
47_All Aux Motors in MMC mode are off sequence
Option-01 1793
M11 Define
See [Option-00]
Defines functionality of input MI11 on I/O extension card.
Option-02 1794
M12 Define
See [Option-00]
Defines functionality of input MI12 on I/O extension card.
Option-03 1795
M13 Define
See [Option-00]
Defines functionality of input MI13 on I/O extension card.
Option-04 1796
M14 Define
See [Option-00]
Defines functionality of input MI14 on I/O extension card.
Option-05 1797
M15 Define
See [Option-00]
Defines functionality of input MI15 on I/O extension card.
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...