PARAMETER REFERENCE TABLES
Parameter Descriptions > Motor Menu
140
Motor-15 2319 Y Torque Filter T
0.001 to 10 Sec
Response time in controlling torque to motor.
Motor-16 2320 Y Slip Filter T
0.001 to 10 Sec
Response time in controlling slip compensation.
Motor-17 2321 Y Torque Cmp Gain 0 to 10*
Gain value for output voltage increase to compensate for voltage drop on
stator resistance at high motor loads in torque compensation function.
For PM motors max value is 5000.
Motor-18 2322 Y Slip Cmp Gain
0 to 10
Gain value for output frequency increase to provide slip compensation at
high motor loads
Motor-19 2323 Y Slip Dev Level
0 to 100%
Slip percentage level to cause over slip trip. Setting of 0 is No Detection.
Motor-20 2324 Y Slip Dev Det T
0 to 10 Sec
Duration slip percentage has to be at before causing over slip trip.
Motor-21 2325 Y Over Slip Trip
0_Alarm and Run
1_Alarm and Decel
2_Alarm and Coast
3_Disabled
Operation when over slip trip occurs.
Motor-22 2326 Y Motor Hunt Gain 0 to 10000
Gain value in detecting shaft speed of a synchronous motor. A sudden
load change can cause shaft speed to fluctuate.
Motor-23 2327 Y Auto restart
0 to 6000 sec
If the number of internal faults defined by [Prot-41] occurs within this
duration, then an auto restart of the VFD will occur.
Motor-24 2328 Y I/F Current
0 to 150%
Percentage of nominal motor current [SET-03] used to regulate AC out
-
put current during I/F control and DC current during PM DC Alignment.
Motor-25 2329 Y PM Bandwidth HS 0 to 600 Hz
Allowable frequency bandwidth around desired frequency in order to
adjust operating frequency to prevent vibrations in motor operation.
Motor-26 2330 Y PMSVC Fltr Gain
0 to 655.35 Sec
Gain value in adjusting the operating frequency from the desired fre
-
quency to prevent vibrations in motor operation.
Motor-27 2331 Y Freq I/F to PM
0 to 599 Hz
When increasing frequency, the frequency to switch modes from I/F
mode to PMSVC mode.
Motor-28 2332 Y Freq PM to I/F
0 to 599 Hz
When decreasing frequency, the frequency to switch modes from PMSVC
mode to I/F mode.
Motor-29 2333 Y I/F fltr time
0 to 6 Sec
Low-pass filter time of current being commanded from I/F Current
[Motor-24].
Motor-30 2334 Y Angle Det Pulse
0 to 3
Value is a multiplier of nominal motor current which is magnitude of pulse
during the angle detection. This is only used when Rotor Zeroing [Motor-
14] is set to 2 or 3.
Motor-31 2335 Y Zero voltage T
0 to 60 Sec
Duration the output is 0V to establish a static startup. Once the system is
at a static startup. The VFD can accurately estimate angles. This parame
-
ter is applicable when SS Normal Start [Prot-42] is not set to 0.
Motor-32 2336 Y Injection Freq
0 to 1200 Hz
Frequency used to determine angle of motor during High Frequency
Injection. Injection Frequency should be at least 100Hz larger than motor's
nominal frequency. Carrier frequency should be 10 times larger than Injec
-
tion Frequency.
Motor-33 2337 Y Injection V
0 to 200 V
Voltage used to determine angle of motor during High Frequency Injec
-
tion.
Motor-34 2338 N Run Time Min
0 to 1439 min
Minutes of the motor run time. Less than 60 seconds is not recorded.
Motor-35 2339 N Run Time Days
0 to 65535 day
Days of the motor run time.
Motor-36 2340 N Motor PF
0 to 1
Power Factor value from motor nameplate
Motor-37 2341 N PM Trq Comp I/F 0 to 5000
PM Torque Compensation in I/F Mode
Motor-38 2342 N PM Trq Comp SVC 0 to 5000
PM Torque Compensation in SVC Mode
Motor-39 2343 N DC-Tun Curr P
0 to 65535
Gain value regulating DC current during DC Alignment of PM motor.
Motor-40 2344 N DC-Tun Curr I
0 to 65535
Integral gain regulating DC current during DC Alignment of PM motor.
CODE
Mod
Bus AR
Display Name
Range
Description
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...