PARAMETER REFERENCE TABLES
Parameter Descriptions > PROTECTION Menu
131
PROT-19 1043 Y PTC/PT100 Sel
0_Alarm and Run
1_Alarm and Decel
2_Alarm and Coast
3_Disabled
Set operation when PTC, PT100, or KTY84 exceed level 2.
PROT-20 1044 Y PTC Level
0 to 100%
Set detection level of PTC. The corresponding value for 100% is the analog
input maximum value
PROT-21 1045 Y OPO Trip
0_Alarm and Run
1_Alarm and Decel
2_Alarm and Coast
3_Disabled
Select operation for Output Phase Loss.
PROT-22 1046 Y OPO Delay
0 to 65.535 Sec
Duration of output phase loss until operation occurs.
PROT-23 1047 Y OPO Current
0 to 100%
Set level of output phase loss.
PROT-24 1048 Y OPO Decel
0 to 65.535 Sec
DC Brake Time of output phase loss.
PROT-25 1049 Y LvX Auto Reset
0_Disable
1_Enable
Set low voltage fault operation to auto reset. Once DC bus voltage returns,
the VFD clears fault and restarts motor.
PROT-26 1050 Y IPO Check Time
0.0 to 600 Sec
Set how often to check for input phase loss.
PROT-27 1051 Y IPO Ripple
(Varies with VFD rating)
An input phase loss is detected when DC bus ripple is higher than IPO Rip
-
ple for duration of IPO Check plus 30 seconds.
PROT-28 1052 Y IPO Trip
0_Alarm and Decel
1_Alarm and Coast
Operation when input phase loss is detected.
PROT-29 1053 Y Derating Type
0_Carrier by I_T
1_Limit Current
2_Limit Carrier
Set how the VFD derates itself.
0 - Limit the carrier wave to reach max load current and temperature.
1 - Limit the current to use max carrier frequency.
2 - Limit the carrier wave to reach max load current and temperature
except when output current is the derating ratio x 130% of output current
in light load.
PROT-30 1054 Y PT100 Level 1
0.0 to 10 V
Level the PT100 reaches for duration for PT100 L-1 Delay causing drive to
back frequency down to PT100 L-1 Freq.
PROT-31 1055 Y PT100 Level 2
0.0 to 10 V
Level the PT100 reaches causing PTC Select [Prot-19] operation.
PROT-32 1056 Y PT100 L-1 Freq
0.0 to 599 Hz
Frequency the VFD reduces to after reaching PT100 Level 1 for duration of
PT100 L-1 Delay.
PROT-33 1057 Y PT100 L-1 Delay 0.0 to 6000 Sec
Duration PT100 has to be above PT100 Level 1 to cause frequency reduc
-
tion to PT100 L-1 Freq.
PROT-34 1058 Y Gnd Fault Lvl
0 to 6553.5%
Percentage of light-load current that current phase unbalance has to reach
for duration of G-Fault Delay [Prot-35] for ground fault to occur.
PROT-35 1059 Y Gnd-Fault Delay 0 to 6553.5 Sec
Duration of current phase unbalance for ground fault to occur.
PROT-36 1060 Y STO Alarm Type 0_STO Latching
1_STO Non-Latch
PROT-37 1061 Y IPF S-Search
0_Disable
1_At Last Freq
2_At Min Freq
Speed search treatment after Instantaneous Power Failure (IPF).
PROT-38 1062 Y Max IPF Time
0 to 20 Sec
Duration power loss has to occur for output to be turned off (coast stop).
PROT-39 1063 Y SS Current Lmt
20 to 200%
Following a momentary power loss, the drive will start speed search oper
-
ation if the output current is greater than PROT-39 value.
PROT-40 1064 Y SS After Fault
0_Disable
1_At Last Freq
2_At Min Freq
Speed search treatment after fault,
PROT-41 1065 Y Auto Restarts
0 to 10
Number of auto restart attempts after fault.
PROT-42 1066 Y SS Normal Start 0_Disable
1_At Max Freq
2_At Start Freq
3_At Min Freq
Speed search treatment for normal start command.
PROT-43 1067 Y Spd Search Gain 1 to 200%
Voltage gain percentage for speed search operation. Reduce value if over
-
load or overcurrent fault occurs.
PROT-44 1068 Y IPF Restart Dly
0 to 5 Sec
Delay for restart after an Instantaneous Power Failure. Set value high
enough to allow residual regeneration voltage to disappear.
CODE
Mod
Bus AR Display Name
Range
Description
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...