PARAMETER REFERENCE TABLES
Parameter Descriptions > VFD Menu
119
Parameter Descriptions > VFD Menu
AR = Adjustable while Running.
CODE Mod
Bus AR Display Name
Range
Description
VFD-00 0256 N VFD Max Freq
0 to 599 Hz
The highest frequency (speed) allowable when running a motor in non-PID
mode. If speed control signal goes higher, motor will not exceed this limit. If
running a MagForce pump, this should be set to the calculated slip fre
-
quency corresponding to the target pump RPM. Refer to
VFD-01 0257 N VFD Start Freq
0-10 Hz
Frequency the VFD initially starts to output. When start frequency is higher
than the minimum output frequency, VFD output will be from start fre
-
quency to the setting frequency.
VFD-02 0258 N VFD Base Freq
VFD-01 to VFD-00 (Hz)
Set to the motor nameplate frequency rating. VFD provides full output volt
-
age at this frequency.
VFD-03 0259 N V/F Pattern
0_Linear
1_1.5 Power
2_Squared
3_V/F Curve 1
4_V/F Curve 2
5_V/F Curve 3
6_V/F Curve 4
7_V/F Curve 5
8_V/F Curve 6
9_V/F Curve 7
10_V/F Curve 8
11_V/F Curve 9
12_V/F Curve 10
13_V/F Curve 11
14_V/F Curve 12
15_V/F Curve 13
V/F curve can be selected from 15 kinds of default settings.
0_Linear pattern maintains a linear V/Hz ratio for constant torque applica
-
tions.
2_Squared pattern maintains a squared V/Hz pattern, ideal for fan or pump
applications.
VFD-04 0260 Y Step Freq-1
0.0 to 600 Hz
Command frequency determined by Multi-function Input Terminals. Refer
to
.
VFD-05 0261 Y Step Freq-2
0.0 to 600 Hz
See [VFD-04].
VFD-06 0262 Y Step Freq-3
0.0 to 600 Hz
See [VFD-04].
VFD-07 0263 Y Step Freq-4
0.0 to 600 Hz
See [VFD-04].
VFD-08 0264 Y Step Freq-5
0.0 to 600 Hz
See [VFD-04].
VFD-09 0265 Y Step Freq-6
0.0 to 600 Hz
See [VFD-04].
VFD-10 0266 Y Step Freq-7
0.0 to 600 Hz
See [VFD-04].
VFD-11 0267 Y Step Freq-8
0.0 to 600 Hz
See [VFD-04].
VFD-12 0268 Y Step Freq-9
0.0 to 600 Hz
See [VFD-04].
VFD-13 0269 Y Step Freq-10
0.0 to 600 Hz
See [VFD-04].
VFD-14 0270 Y Step Freq-11
0.0 to 600 Hz
See [VFD-04].
VFD-15 0271 Y Step Freq-12
0.0 to 600 Hz
See [VFD-04].
VFD-16 0272 Y Step Freq-13
0.0 to 600 Hz
See [VFD-04].
VFD-17 0273 Y Step Freq-14
See [VFD-04].
See [VFD-04].
VFD-18 0274 Y Step Freq-15
0.0 to 600 Hz
See [VFD-04].
VFD-19 0275 Y ACC-2 Time
0.0 to 600 Sec
Alternate acceleration rate for use with automated Acc/Dec type [ADV-06].
VFD-20 0276 Y DEC-2 Time
0.0 to 600 Sec
Alternate deceleration rate for use with automated Acc/Dec type [ADV-06].
Содержание Cerus X-Drive
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 1 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Страница 94: ...COMMUNICATIONS BACnet Communication 94 ...
Страница 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Страница 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...
Страница 102: ...ACCESSORIES Optional Extension Cards 102 ...