45
Service setting manual
EN
SERVICE PARAMETERS
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S1.5
T8 SENSOR
FUNCTION
Selection of function for sensor
connected to input T8.
0- No sensor.
1- RF2, room sensor in circuit 2
2- EF2, sensor for limitation of max.
floor temperature in circuit 2. Max.
floor temperature is set with
parameter S3.11.
3- RLF2, return pipe sensor in circuit
2. Activates limitation of difference
between stand and return pipe and
by that the limitation of max. heating
circuit power. Max. difference is set
with parameter S3.14.
4- RF1, room sensor in circuit 1
5- EF1, sensor for limitation of max.
floor temperature in circuit 1. Max.
floor temperature is set with
parameter S2.11.
6- RLF1, return pipe sensor in circuit
1. Activates limitation of difference
between stand and return pipe and
by that the limitation of max. heating
circuit power. Max. difference is set
with parameter S2.14.
7- BF3, d. h. w circulation with
temperature sensor. Sensor is placed
onto (hot) exit pipe from storage
tank. D. h. w. circulation pump is
activated if temperature increase is
detected. Duration time of circulation
is set with parameter P4.8.
8- SVS, d. h. w. circulation with flow
switch. D. h. w. circulation pump is
activated if contact are closed.
Duration time of circulation is set
with parameter P4.8.
9- BF2, auxiliary sensor in d .h. w.
storage tank. It is installed in upper
third of storage tank. Warming of d.
h. w. will activate only when BF2
sensor detects drop of temperature.
0– NO SEN-
SOR
1- RF2
2- EF2
3- RLF2
4- RF1
5- EF1
6- RLF1
7- BF3
8- SVS
9- BF2
10- AGF
11- RFHP
12- RLKF
13- AGFTK
1