59
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S6.1
MAXIMUM
SOURCE
TEMPERATURE
PROTECTION
With this setting is activated
protection of max. solar collector
or solid fuel boiler temperature.
If solar collector or solid fuel boiler
temprature is exceeded, circulation
pump in solar system will activate
although d. h. w. temperature is
already reached.
0- NO
1- YES
1
S6.2
MAXIMUM
SOURCE
TEMPERATURE
Setting of maximum solar collectors
or solid fuel boiler temperature.
90 ÷ 290 °C
120
S6.3
SOURCE
SAFETY
SWITCH-OFF
TEMPERATURE
If solar collector or solid fuel boiler
emergency shutdown temperature is
exceeded, circulation pump will stop
unconditionally.
120 ÷ 350 °C
160
S6.4
SOURCE
FROST
PROTECTION
If the temperature drops bellow the
set point value (S6.5), the solar pump
switches -on to prevent freezing in
the collectors and pipelines.
NOTE: This setting is suitable only
for climates areas where the
temperature only occasionally
drops bellow the freezing point.
0- NO
1- YES
0
S6.5
SOURCE
TEMPERATURE
FOR FROST
PROTECTION
Setting of temperature by which the
collector's frost protection should
activate.
-20 ÷ 10 °C
4
S6.6
OPERATION
OF LIQUID
FUEL BOILER
Setting if d. h. w. warming with oil
boiler and solar collectors or solid
fuel boiler can operate at the same
time or oil boiler shall activate with
delay after warming with solar
collectors or solid fuel boiler has
been stopped.
-1- PARALELL
0 ÷ 600 MIN-
DELAY OF
LIQUID FUEL
BOILER
120
SERVICE SETTINGS FOR ALTERNATIVE ENERGY
SOURCES
SERVICE PARAMETERS