39
Service setting manual
EN
SETTINGS FOR THE SECOND HEATING CIRCUIT
USER PARAMETERS
Para-
meter
Parameter name
Parameter description
Setting range
Default setting
P3.1
HEAT CURVE
STEEPNESS
Heating curve steepness indicates
what temperature is required for
the heating bodies by a determined
outdoor temperature.
See chapter Heating curve.
0,1 ÷ 2,6
0,5- floor
1,0- radiators
P3.2
PARALLEL
SHIFT OF
HEATING
CURVE
Setting of parallel shift of heating
curve or calculated stand-pipe
temperature.
Use this setting to eliminate
deviation between actual and
required room temperature.
-15 ÷ 15 °C
0
P3.3
DURATION
OF BOOST
HEATING
Duration of boosted room
temperature by changeover from
night to day heating period.
0 ÷ 200 min 0
P3.4
ROOM
TEMP.
INCREASE
BY BOOST
HEATING
Boost room temperature increase
by changeover from night to day
heating period.
0 ÷ 8 °C
3
P3.5
HEAT CURVE
STEEPNESS
FOR
ADDITIONAL
DIRECT
CIRCUITS
Setting of heat curve steepness for
additional direct heating circuits.
0,2 ÷ 2,6
1,2
P3.6
PARALLEL
SHIFT OF
HEATING
CURVE FOR
ADD. DIRECT
CIRCUITS
Parallel shift of heating curve
for additional heating circuits.
Values 16 ÷ 90 set directly the
boiler temperature when additional
direct heating circuit is activated.
-15 ÷ 15 °C
16 ÷ 90 °C