60
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S6.7
CIRCUITS
WITH
DELAYED
ACTIVATION
OF LIQUID
FUEL BOILER
Selection of circuits where oil boiler shall
activate with delay after warming with
solar collectors or solid fuel boiler.
1- domestic hot water
2- heating circuits
3- domestic hot water and heating
circuits
1- D. H. W.
2- CIRCUITS
3- BOTH
1
S6.8
SOLAR PUMP
KICK
FUNCTION
Special algorithm activates the solar
pump to switch -on for short intervals.
This way realistic temperature of
collectors is obtained. This function is
used especially with vacuum (tube)
collectors or with classic collectors if the
sensor is fitted outside of the collector
body.
0- NO
1- YES
0
S6.9
MINIMUM
SOURCE
TEMPERATURE
CONSIDERA-
TION
We define whether and how the
minimum collector or solid fuel
boiler temperature is respected.
0- NO
1- YES
2- YES,
SWITCH-ON
2
S6.10
PUMP
OPERATION
MODE
With this setting, the pump operation
mode is selected.
0 – ON/OFF mode means that the pump
is operating at the maximum speed
1 – RPM mode is used exclusively to
control the speed of the standard
circulation pumps
2 – PWM is used exclusively to control
the speed of the energy-saving solar
circulation pumps
3 – PWM, INVERTIRAN is used ex-
clusively to control the speed of the
energy-saving heating circulation pumps
with a PWM control signal
4 – 0–10V mode is used exclusively to
control the speed of the energy-saving
solar circulation pumps with an analogue
control signal
5 – 10–0V mode is used exclusively to
control the speed of the energy-saving
heating circulation pumps with an
analogue control signal
0- ON/OFF
1- RPM
2- PWM
3- PWM,
INVERT.
4- 0-10 V
5- 10-0 V
1