84
Service setting manual
EN
The W.. controller has a special function installed, which enables simulations of all sen-
sors. With the help of this function, users can test controller operation.
This function is intended for the case of start-up, maintenance or testing of a
controller. Sensor simulation is activated by selecting the screen with hydraulic scheme
display with the
button. Press the
button and hold it for 10 seconds.
The controller will switch over to the simulation operation mode.
Move between sensors by pressing the
button.
With buttons
and
set the temperature value for each selected sensor.
The simulated sensor mark will change from T to S.
Simulation operation mode is deactivated by pressing the
button for 10 seconds or
if no button is pressed for more than 5 minutes.
SENSOR SIMULATION
MARKING AND DESCRIPTION OF TEMPERATURE
SENSORS
Temperature sensors, which contain Pt1000 sensor elements, are marked with »XX/Pt«.
TABLE: resistance of Pt1000 temperature sensors
Temperature
[°C]
Resistance
[Ω]
Temperature
[°C]
Resistance
[Ω]
Temperature
[°C]
Resistance
[Ω]
Temperature
[°C]
Resistance
[Ω]
-20
922
35
1136
90
1347
145
1555
-15
941
40
1155
95
1366
150
1573
-10
961
45
1175
100
1385
155
1592
-5
980
50
1194
105
1404
160
1611
0
1000
55
1213
110
1423
165
1629
5
1020
60
1232
115
1442
170
1648
10
1039
65
1252
120
1461
175
1666
15
1058
70
1271
125
1480
180
1685
20
1078
75
1290
130
1498
185
1703
25
1097
80
1309
135
1515
190
1722
30
1117
85
1328
140
1536
195
1740
BASIC DESCRIPTIONS OF