46
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S1.5
T8 SENSOR
FUNCTION
10- AGF, flue gas temperature sensor
for boiler. Warning is displayed on
the screen, if flue gas temperature
rises above value of parameter S5.18.
11- RFHP, room sensor in ambient
where d. h. w. heat pump is installed.
D. h. w. warming with other heat
sources is disabled if room tempera-
ture is higher as set with parameter
S4.11.
12- RLKF, boiler return-pipe sensor.
Controller maintains min. level of
boiler return-pipe temperature set
with parameter S5.14. For this setting
it is necessary to have a hydraulic
system with primary boiler circula-
tion pump or hydraulic system with
boiler bypass pump (parameter
S4.9=4).
13- AGFTK, flue gases sensor for solid
fuel boiler. Controller blocks liquid
fuel boiler operation if flue gases
exceed temperature setted with
parameter S5.19.
0– NO SEN-
SOR
1- RF2
2- EF2
3- RLF2
4- RF1
5- EF1
6- RLF1
7- BF3
8- SVS
9- BF2
10- AGF
11- RFHP
12- RLKF
13- AGFTK
1
S1.6
DIGITAL INPUT
T1, T6, T8
This setting defines controller
operation mode if short circuit is
detected on input T1, T6 or T8.
0 – Digital input has no function.
1- Day temperature operation mode,
regardless to currently selected
operation mode. See also parameter
S1.9.
2- Additional direct circuit is
connected. Temperature
requirements of additional direct
circuit (P3.5 and P3.6) are also
considered for calculation of
requested boiler temperature.
By schemes with two heat sources
the switchover to other heat
source is done with delay, set with
parameter S5.15.
0– NO
FUNCTION
1- REMOTE
ACTIV.
2- DIR. CIRC.,
DELAYED
SWITCHOVER
3- DIR.
CIRCUIT
4- COOLING
5- BOOST
6- BOILER
LOCKOUT
7- BURNER
COUNTER
1
SERVICE PARAMETERS
Содержание MeiTronic W10