74
Service setting manual
EN
DOMESTIC HOT WATER
D. H. W. WARMING WITH LIQUID FUEL BOILER
With the parameter P4.1 you can set the required d. h. w. temperature for the inactive
time program interval. If the boiler temperature exceeds the maximum allowed boiler
temperature - parameter S5.1 d. h. w will be warmed up to the maximum temperature
set with parameter S4.3. When d. h. w. is warmed, the pump is switched off with delay.
The delay time is set with parameter S4.12.
D. H. W. WARMING WITH SOLID FUEL BOILER
When a solid fuel boiler is in operation, the d. h. w. is warmed to the required d. h. w.
temperature (set with parameter S4.10) independent of the time program.
In case the solid fuel boiler temperature exceeds the maximum boiler temperature -
parameter S5.13, then for the required d. h. w. temperature, the maximum allowed d. h.
w. temperature is set with parameter S4.3.
D. H. W. WARMING WITH A HEATER WITH INTEGRATED HEAT PUMP
In this case, a special operation mode of d. h. w. control is activated by setting the
parameter. S1.4=10 (for sensor T1) or S1.5=11 (for sensor T8). Install a room sensor in
the room, where the heat pump is located, and connect it to the T1 terminal (1, GND)
or T8 terminal (8, GND). The controller will block the d. h. w. warming function from
the central heating boiler for the time the heat pump room is warmer as set with
parameter S4.11.
D. H. W. WARMING WITH SOLAR COLLECTORS
The basic operation of the solar collectors system is determined by switch-on
differences, switch-off differences and minimum temperatures of solar collectors -
parameters P6.1, P6.2 and P6.3.
D. h. w. is heated up to the desired temperature set with parameter S4.10.
When d. h. w is warmed and the temperature of solar collectors exceeds the maximum
temperature of solar collectors - parameter S6.2 and S6.1=1, d. h. w. warming is allowed
up to the maximum temperature of d. h. w - parameter S4.3.
D. h. w. warming is switched off unconditionally, if the d. h. w. temperature exceeds the
maximum temperature - parameter S4.5, or if solar collectors temperature exceeds the
protection temperature - parameter S6.3.
When d. h. w. is warmed with solar collectors, you can set the liquid fuel operation
mode with parameter S6.6, namely:
S6.6= -1, which enables simultaneous operation of both heat sources.
S6.6= 0 ÷ 600, the boiler will be switches on with set delay upon deactivation of the
solar system. The set value represents delay time in minutes.
BASIC DESCRIPTIONS OF
CONTROLLER OPERATION