61
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S6.11
MINIMUM RPM
FOR PUMP
Minimum RPM stage for modulation
of circulation pump.
1- 40 % RPM
2- 55 % RPM
3- 70 % RPM
1- 40 %
2- 55 %
3- 70 %
1
S6.12
MAXIMUM
SPEED TIME AT
PUMP START
When the differential condition is
fulfilled, the circulation pump runs at
max. RPM for a setted time.
Afterwards the pump is running with
RPM modulation (if enabled with
parameter S6.10=1).
5 ÷ 300 s
20
S6.13
MIN. PW-
M/0–10V OF
THE PUMP
Sets the minimum pump speed level.
The setting only applies for the con-
trol of the energy-saving circulation
pump speed.
20 ÷ 50 %
20
S6.14
MAX. PW-
M/0–10V OF
THE PUMP
Set up the maximum pump speed
level. The setting only applies for
the control of the energy-saving
circulation pump speed.
60 ÷ 100 %
100
S6.15
SWITCH-OFF
PWM/0–10V
OF THE PUMP
Set up the maximum pump speed
level. The setting only applies for the
control of the energy-saving
circulation pump speed.
0 ÷ 10 °C
0
S6.16
LOCATION OF
COLD SENSOR
FOR DIFF.
THERMOSTAT
Cold sensor (T8) place of mount, if
it is being used for differential ther-
mostat. In exact we define storage
device which is being warmed with
solar collectors or solid fuel boiler.
1- D. H. W.
TANK
2- HEAT AC-
CUMULATOR
1
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S7.1
HEAT PUMP –
OPERATION
MODE
Configures whether the
heat pump control should be
constantly switched on or
weather-compensated.
1 – PERMA-
NENT
ACTIVATION
2 – WEATH-
ER-COMPEN-
SATED
2
SERVICE SETTINGS FOR ALTERNATIVE ENERGY
SOURCES
SERVICE PARAMETERS
Содержание MeiTronic W10