51
Service setting manual
EN
SERVICE SETTINGS FOR THE SECOND HEATING
CIRCUIT
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S3.1
INFLUENCE
OF ROOM
TEMPERAT.
DEVIATION
Set the influence of room
temperature deviation. Lower
value means lower influence, higher
value means higher influence.
0,0 ÷ 3,0
1
S3.2
INFLUENCE OF
ROOM SENSOR
T8
Setting of room sensor T8 influence
on the operation of second circuit.
1- automatic room sensor influence
- room sensor has no influence if
room unit is connected
- room sensor has influence if
room unit isn't connected
2- room sensor has influence
3- room sensor has no influence
This setting has affect only if S1.5=1.
1- AUTO
2- YES
3- NO
1
S3.3
INFLUENCE OF
ROOM UNIT
RCD
Setting of room unit room RCD
influence on the operation of the
second circuit.
0- room units has no influence.
1- room unit 1 has influence.
2- room unit 2 has influence.
3- room unit 1 and 2 have influence.
0- NO
1- R.U. 1
2- R.U. 2
3- R.U. 1 & 2
2
S3.4
PUMP
OPERATION
MODE
Setting of pump operation mode.
Settings have the following meaning:
1- STAND. (circulation pump of
mixing circuit - regular)
2- pump switches off, if requested
room temperature is reached
(only direct circuit)
3- operation according to time
program P1
4- operation according to time
program P2
5- SEL. PROG. (operation according
to selected time program)
1- STANDARD
2- SWITCH-
OFF
3- PROG. P1
4- PROG. P2
5- SELECTED
PROGRAM
1
S3.5
MINIMUM
STAND-PIPE
TEMPERATURE
Setting of minimum stand-pipe
temperature limitation, when heating
is active.
10 ÷ 90 °C
20
SERVICE PARAMETERS