40
Service setting manual
EN
USER PARAMETERS
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
P4.1
D. H. W.
TEMPERATURE
IN OFF PERIOD
Setting of d. h. w. temperature in OFF
program timer interval.
4 ÷ 70 °C
4
P4.2
PRIORITY OF D.
H. W. WARMING
TO CIRCUIT 1
Setting if d. h. w. heating has priority to
room heating in circuit 1.
0- NO
1- YES
0
P4.3
PRIORITY OF D.
H. W. WARMING
TO CIRCUIT 2
Setting if d. h. w. heating has priority to
room heating in circuit 2.
0- NO
1- YES
0
P4.7
TIME
PROGRAM
FOR D. H. W.
CIRCULATION
Selection of d. h. w. warming time
program which will be used for d. h. w.
circulation.
Setting 1 is first time program for
domestic hot water warming.
Setting 2 is second time program
for domestic hot eater warming.
Setting 3 is selected time program for
domestic hot water warming.
1- PROG. 1
2- PROG. 2
3- SELECT.
PROG.
3
P4.8
RUNNING TIME
FOR D. H. W.
CIRCULATION
PUMP
Setting of running time for d. h. w.
circulation pump. Pump running
period is always followed by the pump
stand-by period.
0 ÷ 600 sec
300
P4.9
STAND-BY TIME
FOR D. H. W.
CIRCULATION
PUMP
Setting of stand-by time for d. h. w.
circulation pump. Pump stand-by
period is always followed by the pump
running period.
0 ÷ 60 min
10
SETTINGS FOR DOMESTIC HOT WATER