Installation manual
EN
DOMESTIC HOT WATER TANK
USE OF TWO SENSORS
The first sensor is placed half-way up the heat exchanger,
and the second one in the upper third of the heater.
In this case, the activation of hot water warming is done
according to the upper sensor, and the deactivation is done
according to the lower sensor. The advantage of using two
sensors is the reduction of the number of boiler switch-ons.
USE OF ONE SENSOR
The sensor is placed above the heat exchanger. The activation
and deactivation of heating is done solely on the basis of one
sensor.
Use of only one sensor is not recommended for the warming of
domestic hot water from boiler in summertime.