56
Service setting manual
EN
SERVICE SETTINGS FOR BOILERS
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S5.1
MAXIMUM
BOILER
TEMPERATURE
Setting of maximal liquid fuel boiler
temperature.
60 ÷ 160 °C
90
S5.2
BURNER
HYSTERESIS
AND
OPERATION
MODE
Setting of burner operation mode
and hysteresis.
-1- Relay is energized if there is no
demand for heating, regardless to
heat source temperature. This way
we block operation of heat sources
with independent controller. Such
control is required for Rotex boilers.
0- relay is energized when there is
need for heating, regardless to heat
source temperature. This way we
activate operation of independent
heat sources, such as (wall hung gas
boiler or heat pump).
1 ÷ 20- burner control hysteresis.
-1- SWITCH-
OFF
0- SWITCH-
ON
1- 20 °C- HYS-
TERESIS
8
S5.3
BOILER
TEMPERATURE
INCREASE FOR
CIRCUIT 1
Setting of boiler temperature in-
crease in comparison with calculated
stand-pipe temperature for circuit 1.
0 ÷ 25 °C
5
S5.4
BOILER
TEMPERATURE
INCREASE FOR
CIRCUIT 2
Setting of boiler temperature
increase in comparison with
calculated stand-pipe
temperature for circuit 2.
0 ÷ 25 °C
5
S5.5
BOILER TEMP.
INCREASE
FOR D. H. W.
WARMING
Setting of boiler temperature
increase in comparison with
requested d. h. w. temperature.
0 ÷ 25 °C
10
S5.6
BOILER
STAND-BY
AT MIN.
TEMPERATURE
Setting of boiler stand-by at
min. boiler temperature.
This setting has affect only if
heating operation mode is active.
0- ON
1- DAY TEMP.
PERIOD
2- OFF
2
S5.7
BURNER
SWITCH-OFF
BY SOLID FUEL
BOILER TEMP.
INCREASE
Setting of solid fuel boiler
temperature increase that causes
liquid fuel boiler to switch off.
Monitoring period is 2 minutes.
0- NO
1 ÷ 5 °C
4