75
Service setting manual
EN
D. H. W. WARMING WITH AN ELECTRIC HEATING BODY INSTEAD OF BOILER
You can program the output for the pump for d. h. w. warming from the boiler (R5) to
control the electric heater for d. h. w. warming by setting the parameter S4.1=2.
D. h. w. will be warmed up to the set desired temperature according to the time
program for d. h. w. warming.
D. H. W. WARMING WITH AN ELECTRIC HEATING BODY AND BOILER
You can program the output for the circulation pump (R6, R7 or R8) to control the
electric heater for d. h. w. warming by setting the parameter S4.9=2 .
D. h. w. will be warmed up to the set desired temperature according to the time
program for d. h. w. warming.
To control the electric heating body, a power relay and a thermal fuse must be
connected.
BASIC DESCRIPTIONS OF
CONTROLLER OPERATION
PRIORITY OF D. H. W. WARMING OVER ROOM HEATING
With parameters P4.2 and P4.3 you can set the priority of d. h. w. warming over room
heating.
RETURN COOLING OF DOMESTIC HOT WATER (RECOOLING)
With parameter S4.4 you can activate return cooling of domestic hot water, if d. h.
w. temperature approaches it maximum temperature. Parameter S4.4 enables you to
select in what manner the d. h. w. will be cooled.