41
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range Default
setting
P5.1
MIN. LIQUID FUEL
BOILER TEMP.
Setting of min. liquid fuel boiler
temperature.
1 ÷ 90 °C
35
P5.2
MIN. SOLID FUEL
BOILER TEMP.
Setting of min. solid fuel boiler
temperature.
10 ÷ 90 °C 55
P5.3
MIN. HEAT
ACCUMULATOR
TEMP.
Setting of min. temperature for heat
transfer from storage tank.
20 ÷ 70 °C 30
SETTINGS FOR BOILERS
SETTINGS FOR ALTERNATIVE ENERGY SOURCES
USER PARAMETERS
Para-
meter
Parameter name
Parameter description
Setting range Default
setting
P6.1
VKLOPNA DIFER-
ENCA VIRA
Setting of difference between solar
collectors or solid fuel boiler
temperature and storage tank or heat
accumulator temperature by which the
circulation pump shall switch-on.
5 ÷ 30 °C
12
P6.2
IZKLOPNA DIFER-
ENCA VIRA
Setting of difference between solar
collectors or solid fuel boiler
temperature and storage tank or heat
accumulator temperature by which the
circulation pump shall switch-off.
1 ÷ 25 °C
4
P6.3
MINIMALNA TEMP.
VIRA
Setting of min. solar collector or solid
fuel boiler temperature to activate the
circulation pump.
10 ÷ 60 °C 35
P6.10
COMPENSATION
OF THE EFFECT
OF BUILDING
ON OUTDOOR
SENSOR
TEMPERATURE
This setting enables compensation of
the effect of heat passing through the
exterior walls of a heated building on
the temperature of the outdoor sensor.
-5.0 ÷ 0.0
°C
-2,0