88
Installation manual
EN
CONNECTION OF
TEMPERATURE SENSORS
IMMERSION SENSOR
Immersion sensor is intended to be installed into immersion tube of boiler, heat
accumulator, d. h. w. storage tank, solar collectors or elsewhere. Make sure that the
sensor rests against the tube walls. Secure the sensor with a fastener or a screw.
SURFACE SENSOR
Install the surface sensor onto the stand-pipe above the bypass pump or after the
mixing valve. Clean the selected spot on the pipe first. Place the sensor onto the
cleaned spot and secure it with the enclosed spring clip.
OUTDOOR TEMPERATURE SENSOR
Install the outdoor temperature sensor onto the facade facing north or north-west,
approximately 2m above ground. Installation above the windows or vents on the
facade facing south is not allowed.
First remove the protective cover and unscrew two screws from the cover. Use the
enclosed wall screw to attach the sensor to the envisaged spot. Introduce the cable
into the sensor through a feedthrough from the bottom side and connect the sensor.
ROOM TEMPERATURE SENSOR
Install the room temperature sensor onto an indoor wall of a living area, which is not
sunlit and distant from heat and draft sources. Remove the cover and screw the base
onto the selected spot approximately 1.5 metres above ground. You can also install it
onto an electrical case or directly onto a wall. A 2-wire signal cable is required for
electrical connection. If there are thermostatic valves installed onto radiators in the
room, where room unit is located, the thermostatic valves have to be fully opened. If
room sensor is connected to T1 terminal, the required parameter setting is S1.4=1. If
room sensor is connected to T8 terminal, the required parameter setting is S1.5=1.
If temperature sensor that is not required in the selected scheme is connected
to T1 or T8 fastener, you must define its operation mode with parameter S1.4
for T1 sensor and with parameter S1.5 for T8 sensor.