44
Service setting manual
EN
SERVICE PARAMETERS
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S1.4
T1 SENSOR
FUNCTION
6- BF3, d. h. w circulation with
temperature sensor. Sensor is placed
onto (hot) exit pipe from storage
tank. D. h. w. circulation pump is
activated if temperature increase is
detected. Duration time of circulation
is set with parameter P4.8.
7- SVS, d. h. w. circulation with flow
switch. D. h. w. circulation pump is
activated if contact are closed.
Duration time of circulation is set
with parameter P4.8.
8- BF2, auxiliary sensor in d .h. w.
storage tank. It is installed in upper
third of storage tank. Warming of d.
h. w. will activate only when BF2
sensor detects drop of temperature.
9- AGF, flue gas temperature sensor
for boiler. Warning is displayed on
the screen, if flue gas temperature
rises above value of parameter S5.18.
10- RFHP, room sensor in ambient
where d. h.w. heat pump is installed.
D. h. w. warming with other heat
sources is disabled if room
temperature is higher as set
with parameter S4.11.
11- RLKF, boiler return-pipe sensor.
Controller maintains min. level of
boiler return-pipe temperature set
with parameter S5.14. For this setting
it is necessary to have a hydraulic
system with primary boiler
circulation pump or hydraulic
system with boiler bypass pump
(parameter S4.9=4).
12- AGFTK, flue gases sensor for solid
fuel boiler. Controller blocks liquid
fuel boiler operation if flue gases
exceed temperature setted with
parameter S5.19.
0– NO
SENSOR
1- RF1
2- EF1
3- RLF1
4- KTF
5- KF2
6- BF3
7- SF3
8- BF2
9- AGF
10- RFHP
11- RLKF
12- AGFTK
1