Output Test: Using this option you can select which test output signals are to be sent to the component contacts. Short
circuits between the wires can be detected and rectified by means of this additional check. For this purpose it is necessary
to configure the test output signals (from the test output signals available).
StartUp Test: If selected, the test is undertaken on switching on the external components. This test is undertaken by opening
and activating the key lock switch to carry out one complete function test and to activate the OUTPUT output. This test is
only requested on starting the machine (on switching on the module).
Filter (ms): This parameter makes it possible to filter the signals that are received from the external contactors. This filter
can be set to between 3 and 250 ms and removes any contact bounce. The time set for the filter affects the calculation of
the total response time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been selected. Using this value you can specify
the maximum time (in ms) between the switching of the two different signals received from the external contacts.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. This text is displayed in the upper part of
the symbol.