9.5.1.1. Network (NETWORK) (max. number = 1)
Using the NETWORK operator, STOP and RESET commands are dis-
tributed via a local network. Using
Network_IN
and
Network_OUT
it is possible to exchange START, STOP and RUN signals between
the various nodes.
Principle of operation
Using this operator you can straightforwardly distribute STOP and
RESET commands via a local MSC network.
Figure 187: Network
The following conditions must be met for the "Network" operator:
1. The input connected to a single or double Network_In input must be connected to the
Network_OUT
output on the
previous module in the network.
2. The
Network_OUT
output connected to a STATUS output or an OSSD output must be connected to the
Network_IN
input on the following module in the local network.
3. The
Stop_IN
and
Reset_IN
inputs must be connected to input devices that act as stop (e.g. E-STOP) or reset devices
(e.g. SWITCH).
4. The
IN
input can be connected as required to the logic (e.g. input function blocks or results of logical combinations).
5. The
Output
output can be connected in the logic as required. The output is "1" (TRUE) if the IN input is "1" (TRUE) and
the function block has been restarted.
Parameter
Enable Network Reset: If selected, the function block can be reset via the network. If not selected, the function block can
only be reset via the local
Reset_IN
input.
Enable Error Out: If selected, the STATUS output
Error_OUT
is available.
Application example:
Figure 188: Application example, network
Network data flow