Operating Instructions
Modular Safety Control System MSC
90
(Translation of the original operating instructions) 2121331-04-04/19
Important!
If Manual Reset is selected, the next input must be used. Example: If Input1 and Input2 are used for
the function block, Input3 must be used for the reset input.
Output Test: Using this option you can select which test output signals are to be sent to the emergency stop device. Short
circuits between the wires can be detected and rectified by means of this additional check. For this purpose it is necessary
to configure the test output signals (from the test output signals available).
StartUp Test: If selected, the test is undertaken on switching on the external components (emergency stop). This test is
undertaken by pressing and releasing the emergency stop to carry out one complete function test and to activate the output.
This test is only requested on starting the machine (on switching on the module).
Filter (ms): Makes it possible to filter the signals that are received from the emergency stop. This filter can be set to between
3 and 250 ms and removes any contact bounce. The time set for the filter affects the calculation of the total response time
of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from the emergency stop is checked.
Simultaneity (ms): This control is only available if the previous parameter has been selected. Using this value you can define
the maximum time (in ms) between the switching of the two signals that are received from the emergency stop.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. This text is displayed in the upper part of
the symbol.
Содержание MSC
Страница 1: ...EN Operating Instructions Installation and use Modular Safety Control System MSC ...
Страница 171: ......
Страница 173: ......