8.4.8. Module AZ-FO4O8
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL0/1 ORANGE
RELA
Y1/4
RED/GREEN
CLEAR1/4 YELLOW
ST
ATUS1/8 YELLOW
Internal err
or
OFF
Flashes 2 or
3 times
OFF
Indicates the physical
addr
ess of the module
RED
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Compatibility err
or
OFF
Flashes 5
times
OFF
Flashes 5 times
Flashes 5 times
Flashes 5
times
Ì
Firmwar
e version not compatible with
MSC-CB. Send to EUCHNER for firm
-
war
e upgrade.
Relay output err
or
OFF
Flashes 4
times
OFF
Flashes 4 times (only the LED cor
-
responding to the
output in the ERROR
mode)
OFF
OFF
Ì
If the pr
oblem persists, send module to
EUCHNER for r
epair
.
Err
or during commu
-
nication with base unit
OFF
Flashes 5
times
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send module to
EUCHNER for r
epair
.
Err
or in another
extension module or MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess
detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
Ì
Change addr
ess of the module (see
section NODE_SEL)
External feedback loop err
or r
elay
category 4
ON
OFF
Flashes 4
times
Flashes 4 times
(only the LED corr
esponding to the
output in the ERROR mode
)
OFF
Ì
Check terminal 5, 6, 7, 8
Internal node detec
-
tion err
or
OFF
Flashes 3
times
OFF
Flashes 3
times
OFF
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Shor
t cir
cuit or
overload detected
OFF
OFF
ON
OFF
OSSD state
CLEAR state
Flashing
Ì
Check output connections
Table 53:
Tr
oubleshooting AZ-FO4O8