Operating Instructions
Modular Safety Control System MSC
58
(Translation of the original operating instructions) 2121331-04-04/19
8.4.6. Modules AC-FO2/AC-FO4
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL
ORANGE
OSSD1/2
RED/GREEN
CLEAR1/2 YELLOW
ST
ATUS1/4 YELLOW
Internal err
or
OFF
Flashes 2 or
3 times
OFF
Indicates the physical addr
ess of
the module
Red
OFF
OFF
Ì
Send module to EUCHNER for repair
.
Compatibility err
or
OFF
Flashes 5
times
OFF
Flashes 5
times
Flashes 5
times
Flashes 5
times
Ì
Firmwar
e version not compatible
with MSC-CB. Send to EUCHNER for firmwar
e upgrade.
OSSD output err
or
OFF
Flashes 4
times
OFF
Flashes 4
times
(only the LED corr
esponding
to the output in the err
or
mode)
OFF
OFF
Ì
Check OSSD1/2 connections.
Ì
If the pr
oblem persists, send
AC-FO2/AC-FO4 to EUCHNER for repair
.
Err
or during communica
-
tion with base unit
OFF
Flashes 5
times
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send
AC-FO2/AC-FO4 to EUCHNER for repair
.
Err
or in another extension
module or MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
Ì
Change addr
ess of the module
(see section NODE_SEL)
Power supply failed on OSSD3/4 (only AC-FO4)
ON
OFF
ON
Red flashing
Flashing
OUTPUT
state
Ì
Connect terminal 13 and 14 to power supply
ST
ATUS output overload
or shor
t cir
cuit
OFF
OFF
ON
OSSD state
CLEAR state
Flashing
Ì
Check ST
ATUS cable
Internal node detection err
or
OFF
Flashes 3
times
OFF
Flashes 3
times
OFF
OFF
OFF
Ì
Send to EUCHNER for r
epair
.
Table 51:
Tr
oubleshooting AC-FO2/AC-FO4
Figur
e 32:
AC-FO2/AC-FO4
Содержание MSC