Operating Instructions
Modular Safety Control System MSC
62
(Translation of the original operating instructions) 2121331-04-04/19
8.4.10. Module O16
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL 0/1 ORANGE
ST
ATUS 1/8 YELLOW
ST
ATUS 9/16 YELLOW
Internal err
or
OFF
Flashes 2 or 3
times
OFF
Indicates the phys
-
ical addr
ess of the
module
OFF
OFF
Ì
Send module to EUCHNER for r
epair
.
Compatibility err
or
OFF
Flashes 5 times
OFF
Flashes 5 times
Flashes 5 times
Ì
Firmwar
e version not compatible with
MSC-CB. Send to EUCHNER for firmwar
e
upgrade.
Err
or during communi
-
cation with base unit
OFF
Flashes 5 times
OFF
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send module to
EUCHNER for r
epair
.
Err
or in another exten
-
sion module or MSC-CB
OFF
ON
OFF
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess detected
OFF
Flashes 5 times
Flashes 5 times
OFF
OFF
Ì
Change addr
ess of the module (see
section NODE_SEL)
Internal node detection err
or
OFF
Flashes 3 times
OFF
Flashes 3 times
OFF
OFF
Ì
Send to EUCHNER for r
epair
.
Shor
t cir
cuit or overload
on the status outputs 1–8
OFF
OFF
ON
OFF
Flashing
OFF
Ì
Check status output connections 1–8
Shor
t cir
cuit or overload
on the status outputs 9–16
OFF
OFF
ON
OFF
OFF
Flashing
Ì
Check status output connections 9–16
No supply to the status outputs 1–8
OFF
OFF
ON
OFF
Alternately flash
-
ing
OFF
Ì
Connect pin 5 to the supply
No supply to the status outputs 9–16
OFF
OFF
ON
OFF
OFF
Alternately flash
-
ing
Ì
Connect pin 6 to the supply
Table 55:
Tr
oubleshooting O16
Figur
e 36:
O16
Содержание MSC