63
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
8.4.11. Modules SPM0, SPM1, SPM2
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL
ORANGE
ENC*
YELLOW
PROX YELLOW
SH
YELLOW
Internal err
or
OFF
Flashes 2 or
3 times
OFF
Indicates the physical
addr
ess of the module
OFF
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Compatibility err
or
OFF
Flashes 5
times
OFF
Flashes 5
times
Flashes 5
times
Flashes 5
times
Ì
Firmwar
e version not com
-
patible with MSC-CB. Send to EUCHNER for firmwar
e
upgrade.
Internal encoder err
or
OFF
Flashes 3
times
OFF
Flashes 3
times
OFF
OFF
Ì
Replace encoder
Ì
Send to EUCHNER for r
epair
Internal pr
oximity
switch err
or
OFF
Flashes 3
times
OFF
Flashes 3
times
Ì
Replace pr
oximity switch
Ì
Send to EUCHNER for r
epair
Internal node detec
-
tion err
or
OFF
Flashes 3
times
OFF
Flashes 3
times
OFF
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Extension module of the same type with the same addr
ess
detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
Ì
Change addr
ess of the mod
-
ule (see section NODE_SEL)
Encoder not connect
-
ed, but r
equested by
configuration
OFF
OFF
Flashes 3 times**
Flashes 3 times**
OFF
OFF
Ì
Check connection and power supply for the encoder/pr
ox
-
imity switch
Ì
Check input fr
equency (in
range)
Pr
oximity switch
not connected, but requested by config
-
uration
OFF
OFF
Flashes 3 times**
OFF
Flashes 3 times**
OFF
*
IF SPM0 MODULE NOT FITTED
**
IF ERROR ON A SINGLE CHANNEL, THE FOLLOWING ERROR INFORMA
TION IS INDICA
TED IN SUCCESSION:
FIRST THE ERROR, THEN THE ERRONEOUS CHANNEL.
Table 56:
Tr
oubleshooting SPM0, SPM1, SPM2
Figur
e 37:
SPM1, SPM2