59
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
8.4.7. Module AZ-FO4
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL0/1 ORANGE
RELA
Y1/4
RED/GREEN
CLEAR1/4 YELLOW
Internal err
or
OFF
Flashes 2 or 3
times
OFF
Indicates
the phys
-
ical addr
ess of the
module
RED
OFF
Ì
Send module to EUCHNER for r
epair
Compatibility err
or
OFF
Flashes 5 times
OFF
Flashes 5 times
Flashes 5 times
Ì
Firmwar
e version not compatible with
MSC-CB. Send to EUCHNER for firm
-
war
e upgrade.
Relay output err
or
OFF
Flashes 4 times
OFF
Flashes 4 times
(only the LED corr
e-
sponding to the output in the ERROR mode)
OFF
Ì
If the pr
oblem persists, send module
to EUCHNER for r
epair
.
Err
or during communica
-
tion with base unit
OFF
Flashes 5 times
OFF
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send module
to EUCHNER for r
epair
.
Err
or in another extension
module or MSC-CB
OFF
ON
OFF
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess detected
OFF
Flashes 5 times
Flashes 5 times
OFF
OFF
Ì
Change addr
ess of the module (see
section NODE_SEL)
External feedback loop err
or r
elay category 4
ON
OFF
Flashes 4 times
Flashes 4 times
(only the LED corr
esponding to the output in
the ERROR mode)
Ì
Check terminal 5, 6, 7, 8
Internal node detection err
or
OFF
Flashes 3 times
OFF
Flashes 3 times
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Table 52:
Tr
oubleshooting AZ-FO4
Figur
e 33:
AZ-FO4