169
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
CODE
FAIL
SOLUTION
1D ÷ 31D
Error on microcontrollers
RESTART SYSTEM. IF THE ERROR PERSISTS, SEND THE MODULE TO
EUCHNER FOR REPAIR.
32D ÷ 63D
Fault on main printed circuit board
64D ÷ 95D
Error in the communication between the modules
96D ÷ 127D
Error on the M-A1 memory card
REPLACE M-A1 MEMORY CARD
128D ÷ 138D
Error on the module AZ-FO4, relay 1
RESTART SYSTEM. IF THE ERROR PERSISTS, SEND THE MODULE TO
EUCHNER FOR REPAIR.
139D ÷ 148D
Error on the module AZ-FO4, relay 2
149D ÷ 158D
Error on the module AZ-FO4, relay 3
159D ÷ 168D
Error on the module AZ-FO4, relay 4
128D ÷ 191D
Error on the encoder interface on the SPM modules
RESTART SYSTEM. IF THE ERROR PERSISTS, SEND THE MODULE TO
EUCHNER FOR REPAIR.
192D ÷ 205D
Error OSSD1
206D ÷ 219D
Error OSSD2
220D ÷ 233D
Error OSSD3
234D ÷ 247D
Error OSSD4
Table 79: Overview of error codes, internal malfunction
9.6.4. Error log file
The error log file can be displayed using the
button on the default toolbar
(password required: level 1)
A table is displayed with the last 5 errors that have occurred since the scheme was last sent to the MSC or the last time
the error log was deleted (button:
)
Figure 207: Error log file