Installation and connection
Doc. no. BA012498_03
19 / 112
GB
• NOVA Slave tunable white (colour temperature of 2700–6500 K).
Each tunable white light is powered by the Light Control Box via two con-
nection cables. You must always insert the cable in sockets with the same
label (“ww”/”cw”).
The Light Control Box (tunable white) has two channels (C1, C2) for lighting
control.
Any up-to-date network cable, type Cat5 or higher, can be used as
the RJ-45 patch cable.
NOTE!
Do not connect cables to incorrect sockets!
Connecting cables to incorrect sockets may lead to incorrect light colours.
Note the maximum cable length!
The RJ-45 connection cable must not exceed 10 metres.
Connection to be used for ESYLUX lights only!
Only the specified ESYLUX lights may be connected to the RJ-45 interfac-
es. Other equipment such as Internet routers or lights designed to be pow-
ered via a LAN cable (power over Ethernet) could be irreparably damaged by
connecting them to the RJ-45 jacks.
4.3.5 Connecting DALI switch devices
DALI switch devices can also be connected to the DALI interfaces C1 and
C2. DALI switch devices can be used to connect non-DALI-compatible
equipment such as fans or screen controllers.
The DALI switch devices are available as accessories. By default, the model
SW DALI Full Automation (item no. EP10427473) is set to fully automatic
with a off delay time of 30 minutes. By default, the model SW DALI Semi
Automation (item no. EP10427480) is set to semi-automatic with a off
delay time of six minutes. You can change these factory settings on both
models via the remote control. For more information about these devices,
see our website www.esylux.com.
A maximum of two DALI groups can be connected to the DALI interfaces C1
and C2. A maximum of 25 DALI devices can be connected in each group,
with the groups being powered via the DALI bus. The parameters are auto-
matically applied to the electronic ballasts via broadcast.
The DALI interfaces are numerically assigned to the lighting channels. For
example, DALI interface C2 corresponds to the lighting channel C2.
You can change the assignment of the DALI interfaces DALI C1
and C2 to the lighting channels C1 and C2 (RJ-45 connections).
See Chapter
“DALI Map”
page 65.