The remote control menu <Programming>
Doc. no. BA012498_03
53 / 112
GB
For more information on setting the target brightness, see Chapter
“Light set value” page 56.
80 cm
450 Lux
The light sensor must be calibrated with three measurements at least once
per lighting channel. We recommend three measurements per channel for
optimum illumination results.
If a lighting channel is extended with DALI louvre lights, position
the light with the light sensor in the darkest area of the room.
This is the only way to ensure even the darkest area is sufficiently
lit.
The sub-menu items for <Channel 1> and <Channel 2> are identical. The cali-
bration must be performed individually for each lighting channel. During the
calibration, only the lighting channel that is being calibrated is illuminated.
Calibrating a light sensor:
1. Select the <Programming> menu item and confirm the selection with
the
button.
2. Press the
button to activate programming mode.
3. Select the <Calibration> menu item and confirm the selection with
the
button.
4. Select the
button to choose the menu item <Channel 1>, for
example, and confirm the selection with the
button.
The lighting on channel 1 is switched on at maximum brightness.
The other lighting channels are not active. The light sensor meas-
ures the brightness.
Greater precision
through repeti-
tion
Calibration
procedure