Prothermo NMT532
Adjustment and settings
Hauser
39
7.4
Configuring NMT532 with NMS8x/NMR8x/NRF81
NMS8x, NMR8x and NRF81 are specifically designed to recognize NMT532 as HART
Master. Terminals E1 and E2 or B3 and C3 of NMR8x, NRF81 and NMS8x are connected
to NMT532 with a local HART cable.
Connection from NMS8x, NMR8x and NRF81 to NMT532 is required for Ex Approval.
Follow the connection instructions in the separate BA01025G operating instructions,
"Terminal connection."
7.4.1
Preparation for configuring NMS8x/NMR8x/NRF81
NMS8x, NMR8x and NRF81 must be set to default before connecting to NMT532.
Setting procedure
1. From the Expert menu, choose
Input/Output → HART device → HART device(s) →
NMT device configuration
.
2. Select
"Yes"
for
Config. device?
3. Enter the bottom temperature element in
Bottom point
(see diagram below).
This completes the setting procedure.
a
A0038608
30
Position of the bottom-point temperature element
a
Distance between the bottom-point temperature element to the reference (tank bottom or reference plate)
Default a is 500 mm (19.69 in), but this can be modified as needed.
Liquid temperature display
Item
Details
Navigation
Operation → Temperature → Liquid temp
Description
Displays the average or spot temperature of the measured liquid.
Additional information
Read access: Operator
Write access: -