Prothermo NMT532
Installation
Hauser
31
5.5.8
Mounting on pressurized tank
Pressurized tank is required to install a thermo well to protect the probe from the pressure.
1
2
3
4
5
6
7
8
A0038605
22
Thermo well for a pressurized tank
1
NMS8x / NMS5
2
Ball valve
3
Measuring wire
4
Displacer
5
Stilling well
6
Calibration / maintenance chamber
7
NMT532
8
Thermo well
• If the pressure inside a tank exceeds the atmospheric pressure (absolute pressure
1 bar, 100 kPa, 14.5 psi), install a thermo well (protective pipe) with no holes or
slits onto NMT532. However, NMS8x requires a stilling well with holes and slits.
• NMT532 is installed in the thermo well (protective pipe) from the top of the tank
nozzle.
• Cover the bottom of the thermo well for NMT532 and weld it to protect the probe
from the pressure.
1
A0038606
23
Thermo well welding
1
Welding point