Operation
Prothermo NMT532
56
Hauser
Code
Display
Details
11
#5 element open
12
#5 element short
13
#6 element open
14
#6 element short
23
#0 element over range
24
Memory defect (ROM)
29
Element exposed (liquid level below #1 element position)
41
Memory defect (RAM)
42
Memory defect (EEROM)
Code
Display
Details
VH81
Temperature Unit
(Temperature unit)
Item type
Selection
Default
°C
Selection
°C, °F, K
Screen used to select the temperature display unit.
Based on the HART configuration, °C (HART code: 32), °F (HART code:
33), and K (HART code: 35) are available.
Leave this parameter in °C if you are changing the default °C in
the host gauge (NMS8x, NMR8x, NRF81, NMS5, NMS7,
NRF590, TMD1) to another unit.
VH82
Element Number
(Number of
temperature
measurement
elements)
Item type
Read / Write
Default
2
Range
1 to 16
The number of available temperature measurement elements is
entered. This function is mainly used with the NMT532.
Do not change the default parameter on the NMT532. The
number of elements is predetermined by the customer. Changing
the default parameter may cause erroneous calculations or
unnecessary error displays.
L
CAUTION
Changing the parameters:
Do not change the default parameter on the NMT532. The number of
elements is predetermined by the customer.
‣
Changing the default parameter may cause erroneous calculations
or unnecessary error displays.
VH83
No. of Preambles
(Number of
preambles)
Item type
Read / Write
Default
5
Range
2 to 20
Sets the number of preambles for HART communication.
L
CAUTION
Changing the value:
Do not change the default value.
‣
This may cause erroneous calculations or unnecessary error
displays.
VH84
Distance Unit
(Distance unit)
Item type
Selection
Default
mm
Selection
ft., m, inch, mm