Electrical connection
Prothermo NMT532
32
Hauser
6
Electrical connection
6.1
Terminal connection
6.1.1
NMT532 (Ex ia) intrinsically safe connection
NMT532, which uses intrinsically safe local HART communication, must be connected to
the device's intrinsically safe terminal to be connected. Refer to the intrinsic safety
regulations for establishing wiring and field device layout.
2
1
A
H2- H2+ H1- H1+
FG
A0038528
24
NMT532 terminal (ATEX
・
Ex ia)
A
Temperature data / NMT532 intrinsically safe 2-wire HART communication (see Information)
1
Shielded twisted pair wire or steel-armored wire
2
Standard aluminum (die-cast plug)
Only a metal cable gland may be used. The shielded wire on the HART communication
line must be grounded.
Connection table
Connection to NRF590
Connection to NMS5
Connection to NMS8x/NMR8x/NRF81
+ Terminal
24, 26, 28
+ Terminal
24
+ Terminal
E1
- Terminal
25, 27, 29
- Terminal
25
- Terminal
E2
+H1 and +H2 are + terminals, and -H1 and -H2 are - terminals.