Polaris 1000 

User

’s Manual

 

 

 

 
 

2017/11/06    Version : 1.3us 

DAE Instrument Corp.     

http://www.DAEinstrument.com/

 

Содержание Polaris 1000

Страница 1: ...Polaris 1000 User s Manual 2017 11 06 Version 1 3us DAE Instrument Corp http www DAEinstrument com...

Страница 2: ...Polaris 1000 User s Manual Page 2...

Страница 3: ...p All rights reserved DAE Controls LLC 2707 Golfview Dr 103 Troy Michigan 48084 USA Tel 1 248 635 3708 Fax 1 248 822 8138 e mail info DAEcontrols com DAE Headquarters 5F No 157 Xinhu 1st Road Neihu Di...

Страница 4: ...the wiring diagram designated in this manual 6 Guard against dust and water damage 7 Make sure all power sources to be connected to the product have been shut off before installing 8 If the equipment...

Страница 5: ...allow air to circulate Reposition any extraneous wiring that is on the Polaris Maintenance Check to make sure that the wiring contacts are tight and making good contact tighten any terminal screws th...

Страница 6: ...11 2 3 MOUNTING PROCEDURE 13 2 4 BEFORE INSTALLATION 13 2 5 CONDUIT AND WIRE INGRESS 14 2 6 METER INSTALLATION 15 2 7 CT INSTALLATION 15 2 8 WIRING DIAGRAM 17 2 9 MEASURING MULTIPLE LOADS WITH ONE ME...

Страница 7: ...0A Optional solid core CTs available in 50 200A Parallel up to three sets of CTs for cumulative reading 1 3 Certifications UL CUL Listed 1 4 Specifications Item Description Frequency 50 60 Hz Working...

Страница 8: ...tions 3 1 phase 2 wire 120V 1 or 2 phase 3 wire 120 208 240V 3 CT Rating 200 50 200A depends on CT current range 400 400A 600 600A Water meter option Water meter pulse input is an optional feature whi...

Страница 9: ...is a sophisticated energy meter with multiple capabilities and functions Before installation be sure to read and understand this section and the appropriate wiring diagrams Installation of this devic...

Страница 10: ...B C Phases A B C phase voltage inputs indicator P Watthour test constant indicator Kt 1Wh 1000 imp kWh Load Load status indicator DI Water meter pulse input indicator Terminal Cover To cover the termi...

Страница 11: ...tage input 22 VN Phase N voltage input CT input terminals 13 CT A Phase A CT input 14 CT A Phase A CT input 15 CT B Phase B CT input 16 CT B Phase B CT input 17 CT C Phase C CT input 18 CT C Phase C C...

Страница 12: ...the wires are screwed tightly onto the terminals and making good contact 3 Recommended wire size Terminal type Wire range Voltage input 10 18 AWG screw torque 16 lb inch CT input 14 22 AWG screw torq...

Страница 13: ...2 4 Before Installation 1 Check that the ratings and specifications of the model to be installed is suitable for its intended application 2 Verify that the dedicated CT being used is compatible with...

Страница 14: ...1 2 or 3 4 conduit For voltage and CT wirings cut open the knockout for 3 4 conduit Note Please use UL certified cables and conduits 2 Special terminal cover An alternate terminal cover is also avail...

Страница 15: ...e that the direction and orientation of the CTs with wiring are consistent With solid core CTs the wire must be threaded through the CT which would necessitate disconnecting the wire from the load Wit...

Страница 16: ...se refer to section 2 2 on Terminals 2 Solid core CT installation Load side With solid core CTs the wire must be threaded through the CT which would necessitate disconnecting the wire from the load Me...

Страница 17: ...Wiring Diagram 1 1 phase 2 wire VAN 120V Note Please install a fuse for each voltage input Except the phase N 2 1 or 2 phase 3 wire VAN VBN 120V VAB 208 240V Note Please install a fuse for each volta...

Страница 18: ...CTs must be in the same direction Each of the CTs for the same phase on different loads must be connected to the correct polarity CT white wire to the CT terminal on the meter and the CT black wire t...

Страница 19: ...y The power up sequence of the Polaris shows the following information on the display Display Shows Example Description Range 1 8 8 8 8 8 8 LED display test 2 A1 xxx Reserved 3 b1 xx Reserved 4 r xxx...

Страница 20: ...ively c Check to make sure that power is being supplied from the power source to the voltage input d Check that the power source voltage is within the rated power supply e Check to make sure that the...

Страница 21: ...wiring is connected properly b Check the voltage input terminals are not damaged The accumulation of kWh does not match total consumption a Check to make sure the voltage input is continuously 24 hou...

Страница 22: ...CT input of the Polaris can only accept milli amps which matches DAE s dedicated CTs Connecting a regular 5A output CT directly will thus damage the Polaris meters Q Can the CT lead wire be extended A...

Страница 23: ...used by having the phases reversed voltage and current phases are not properly matched or there may be some run down equipment that are in need of repair or replacement Check to make sure that the vol...

Страница 24: ...tract tort or otherwise shall not exceed the purchase price paid by Customer for the products claimed 6 2 Return Policy All returned material must be in good as new and in salable condition A 20 resto...

Страница 25: ...circuit Our contact information US Website www DAEcontrols com US Email info DAEcontrols com US Phone 1 248 635 3708 International Website www DAEinstrument com International Email info DAEinstrument...

Страница 26: ...Polaris 1000 User s Manual Page 26...

Страница 27: ...Polaris 1000 User s Manual Page 27...