Proline Promass E TB2 HART
Commissioning
Hauser
55
10.4.2 Configuring the current outputs
The two wizards
Current output 1-2
guide you systematically through all parameters that have to
be set in the configuration of the respective current output.
Navigation path
"Setup" menu
®
Current output 1
"Setup" menu
®
Current output 2
Sequence of the wizard
Part 1 (corresponding part 2: next page)
Assign current
output
Off
Mass flow
Volume flow
Density
Temperature
Mass flow unit
Volume flow unit
Density unit
Temperature unit
Current span
4 mA value
20 mA value
Failure mode
...
Min.
Defined value
Failure current
End of wizard
*
4...20 mA
NAMUR
4...20 mA US
4...20 mA
Fixed current
A0013796-EN
å
12
"Current output 1-2" in the "Setup" menu (Part 1)
Off* = Option only for current output 2