Modbus RS485 Register Information
Proline Promag 300 Modbus RS485
246
Hauser
"Variable adjust" submenu
Navigation: Expert → Sensor → Sensor adjustm. → Variable adjust
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Vol. flow offset (1831)
5521 to 5522
Float
Read / Write
Signed floating-point number
Vol. flow factor (1832)
5519 to 5520
Float
Read / Write
Positive floating-point number
Mass flow offset (1841)
5525 to 5526
Float
Read / Write
Signed floating-point number
Mass flow factor (1846)
5523 to 5524
Float
Read / Write
Positive floating-point number
Conduct. offset (1848)
5529 to 5530
Float
Read / Write
Signed floating-point number
Conduct. factor (1849)
5527 to 5528
Float
Read / Write
Positive floating-point number
Corr. vol offset (1866)
2044 to 2045
Float
Read / Write
Signed floating-point number
Corr. vol factor (1867)
2076 to 2077
Float
Read / Write
Positive floating-point number
Temp. offset (1868)
2046 to 2047
Float
Read / Write
Signed floating-point number
Temp. factor (1869)
2042 to 2043
Float
Read / Write
Positive floating-point number
"Calibration" submenu
Navigation: Expert → Sensor → Calibration
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Nominal diameter (2807)
2048 to 2057
String
Read
DNxx / x"
Cal. factor (6522)
2313 to 2314
Float
Read
Positive floating-point number
Zero point (6546)
2870 to 2871
Float
Read
Signed floating-point number
Cond. cal. fact. (6718)
19806 to 19807
Float
Read
0.01 to 10
000
6.3.3
"I/O config." submenu
Navigation: Expert → I/O config.
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
I/O 1 to n terminals (3902–1 to n)
1: 6541
2: 6542
3: 6543
4: 6544
Integer
Read
0 = Not used
1 = 26-27 (I/O 1)
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
I/O 1 to n info (3906–1 to n)
1: 8659
2: 8660
3: 8661
4: 8662
Integer
Read
1 = MODBUS
2 = Configurable
3 = Not configurable
254 = Not plugged
255 = Invalid
I/O 1 to n type (3901–1 to n)
1: 6417
2: 6418
3: 6419
4: 6420
Integer
Read / Write
0 = Off
0 = Curr.output
0 = Current input
0 = Status input
0 = PFS output
Apply I/O config (3907)
8665
Integer
Read / Write
0 = Yes
1 = No
Alteration code (2762)
6427
Integer
Read / Write
Positive integer
*
Visibility depends on order options or device settings