Description of device parameters
Proline Promag 300 Modbus RS485
114
Hauser
t
I [mA]
a =
b =
A0028100
I
Current
t
Time
With
Forward/Reverse
option
This option is not possible in this case as the values for the
0/4 mA value
parameter
(→ 108) and
20 mA value
parameter (→ 109) have different signs.
With
Rev. flow comp.
option
Flow components outside the span are buffered, balanced and output after a maximum
delay of 60 s.
t
I [mA]
S = A
S
A
A0028101
I
Current
t
Time
S
Flow components saved
A
Balancing of saved flow components
Damping out. 1 to n
Navigation
Expert → Output → Curr.output 1 to n → Damping out. 1 to n (0363–1 to n)
Prerequisite
One of the following options is selected in the
Assign curr.
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
• CorrConductivity
• Temperature
• Electronic temp.
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
*
Visibility depends on order options or device settings