Proline Promag 300 Modbus RS485
Description of device parameters
Hauser
77
Off value
Navigation
Expert → Sensor → Process param. → Low flow cut off → Off value (1804)
Prerequisite
One of the following options is selected in the
Assign variable
• Volume flow
• Mass flow
• Correct.vol.flow
Description
Use this function to enter a switch-off value for low flow cut off. The off value is entered as
a positive hysteresis from the on value→ 76.
User entry
0 to 100.0 %
Factory setting
50 %
Additional information
Example
1
A
Q
t
2
H
1
2
3
4
A
A0012887
Q
Flow
t
Time
H
Hysteresis
A
Low flow cut off active
1
Low flow cut off is activated
2
Low flow cut off is deactivated
3
On value entered
4
Off value entered
Pres. shock sup.
Navigation
Expert → Sensor → Process param. → Low flow cut off → Pres. shock sup. (1806)
Prerequisite
One of the following options is selected in the
Assign variable
• Volume flow
• Mass flow
• Correct.vol.flow
Description
Use this function to enter the time interval for signal suppression (= active pressure shock
suppression).
User entry
0 to 100 s
Factory setting
0 s