Proline Promag 300 Modbus RS485
Description of device parameters
Hauser
109
The operational range of the measuring device is defined by the values entered for the
0/4
mA value
parameter (→ 108) and
20 mA value
parameter (→ 109). If the
effective flow exceeds or falls below this operational range, the diagnostic message
S441 Curr.output 1 to n
is displayed.
Configuration example B
Measuring mode with
Forward/Reverse
option
Q
20
0
I [mA]
4
3
1
2
0
A0013758
I
Current
Q
Flow
1
Value assigned to the 0/4 mA current
2
Forward flow
3
Reverse flow
The current output signal is independent of the direction of flow (absolute amount of the
measured variable). The values for the
0/4 mA value
20 mA
value
parameter (→ 109) must have the same sign. The value for the
20 mA value
parameter (→ 109) (e.g. reverse flow) corresponds to the mirrored value for the
20
mA value
parameter (→ 109) (e.g. forward flow).
Configuration example C
Measuring mode with
Rev. flow comp.
option
If flow is characterized by severe fluctuations (e.g. when using reciprocating pumps), flow
components outside the measuring range are buffered, balanced and output after a
maximum delay of 60 s → 110.
20 mA value
Navigation
Expert → Output → Curr.output 1 to n → 20 mA value (0372–1 to n)
Prerequisite
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Use this function to enter a value for the 20 mA current.
User entry
Signed floating-point number
Factory setting
Depends on country and nominal diameter→ 212
Additional information
Description
Positive and negative values are permitted depending on the process variable assigned in
the
Assign curr.
parameter (→ 106). In addition, the value can be greater than or