Proline Promag 300 Modbus RS485
Modbus RS485 Register Information
Hauser
235
"Config. backup" submenu
Navigation: Expert → System → Config. backup
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Operating time (0652)
2631
Integer
Read
Days (d), hours (h), minutes (m) and
seconds (s)
Last backup (2757)
6430
Integer
Read
Days (d), hours (h), minutes (m) and
seconds (s)
Config. managem. (2758)
5500
Integer
Read / Write
0 = Cancel
1 = Execute backup
2 = Restore
4 = Clear backup
5 = Compare
Backup state (2759)
5502
Integer
Read
1 = Backup in progr.
2 = Restore in progr
4 = Delete in progr.
5 = Comp. in progr.
6 = Restoring failed
7 = Backup failed
251 = None
Compar. result (2760)
5514
Integer
Read
0 = Set. identical
1 = Set. not ident.
2 = No backup
3 = Check not done
4 = Backup corrupt
5 = Dataset incomp.
"Diagn. handling" submenu
Navigation: Expert → System → Diagn. handling
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Alarm delay (0651)
6808 to 6809
Float
Read / Write
0 to 60 s
"Diagn. behavior" submenu
Navigation: Expert → System → Diagn. handling → Diagn. behavior
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Diagnostic no. 302 (0739)
2312
Integer
Read / Write
2 = Warning
3 = Alarm
Diagnostic no. 531 (0741)
2397
Integer
Read / Write
0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
Diagnostic no. 441 (0657)
4742
Integer
Read / Write
0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
Diagnostic no. 442 (0658)
4919
Integer
Read / Write
0 = Off
1 = Logbook only
2 = Warning
3 = Alarm
Diagnostic no. 443 (0659)
5000
Integer
Read / Write
0 = Off
1 = Logbook only
2 = Warning
3 = Alarm