Proline Promag 300 Modbus RS485
Description of device parameters
Hauser
115
Description
Use this function to enter a time constant for the reaction time of the current output signal
to fluctuations in the measured value caused by process conditions.
User entry
0.0 to 999.9 s
Factory setting
1.0 s
Additional information
Entry
Use this function to enter a time constant (PT1 element
) for current output damping:
• If a low time constant is entered, the current output reacts particularly quickly to
fluctuating measured variables.
• On the other hand, the current output reacts more slowly if a high time constant is
entered.
Damping is switched off if
0
is entered (factory setting).
Response time
Navigation
Expert → Output → Curr.output 1 to n → Response time (0378–1 to n)
Prerequisite
One of the following options is selected in the
Assign curr.
• Volume flow
• Mass flow
• Correct.vol.flow
• Flow velocity
• Conductivity
• CorrConductivity
• Temperature
• Electronic temp.
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Displays the response time. This specifies how quickly the current output reaches the
measured value change of 63 % of 100 % of the measured value change.
User interface
Positive floating-point number
Additional information
Description
The response time is made up of the time specified for the following dampings:
• Current output damping → 114
and
• Depending on the measured variable assigned to the output.
Flow damping
3)
proportional transmission behavior with first order delay
*
Visibility depends on order options or device settings